Refrigeration Compressor Rated Return Gas Temperature #1187

Open
mdahlhausen opened this issue Aug 30, 2021 · 1 comment
Open

Refrigeration Compressor Rated Return Gas Temperature #1187

mdahlhausen opened this issue Aug 30, 2021 · 1 comment
Labels
Feature Request OS Prototypes Improvements to the OS prototype models.

Comments

@mdahlhausen
Copy link
Collaborator

From @lymereJ:
I noticed that the prototype models using “Low Temp” compressors end up in the IDF file being setup with a rated return gas temperature of 18.3 deg. C and a rated subcooling delta C of 0. According to AHRI Standard 540, the latter is expected but, if I am not mistaken, the former should be 4.44 deg. C (40 deg. F) as the compressors are setup as subcritical. I looked to see if we were using the setRatedReturnGasTemperature() method in the code base but it looks like we are not, so I’m guessing that it’s the default value assumed by OpenStudio. Unless the curves were indeed derived at a rated return gas temperature of 18.3 deg. C or if I am not missing something else, we should probably modify the code to set that value based on the actual rated conditions. This does impact simulation results a bit. The DOE Commercial Prototype Models follow a slightly different approach to model refrigeration systems so I’m not sure how these curves were developed.
image

@mdahlhausen
Copy link
Collaborator Author

Looks like we don't set the return gas temperature in the compressor constructor:
https://github.com/NREL/openstudio-standards/blob/master/lib/openstudio-standards/prototypes/common/objects/Prototype.refrigeration.rb#L352-L379

Two options are:

  1. In the constructor method, set a default return gas temperature, which is possibly determined from other properties of the compressor.

  2. Add a column to the compressor data that indicates the return gas temperature.

I'm fine with either. How common is it that this will be customized? If not often, I lean towards a default temperature. However it is nice to document assumptions like these in the data, rather than having them be set in the code.

@mdahlhausen mdahlhausen added Feature Request OS Prototypes Improvements to the OS prototype models. labels Aug 30, 2021
Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment
Labels
Feature Request OS Prototypes Improvements to the OS prototype models.
Projects
None yet
Development

No branches or pull requests

1 participant