Notifications
You must be signed in to change notification settings - Fork 19
/
deif.py
197 lines (163 loc) · 6.55 KB
/
deif.py
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
from itertools import chain
import device
import probe
from register import *
from utils import getbits
class Reg_DEIF_unit:
def __init__(self, *args, conv, **kwargs):
super().__init__(*args, **kwargs)
self.conv = conv
def update(self, val):
if val is not None:
val = self.conv(val)
return super().update(val)
class Reg_DEIF_unit_s16(Reg_DEIF_unit, Reg_s16):
pass
class Reg_DEIF_unit_u16(Reg_DEIF_unit, Reg_u16):
pass
class Reg_DEIF_alarm(Reg):
def __init__(self, base, count, *args, level, offset=0, **kwargs):
super().__init__(base, count, *args, **kwargs)
self.level = level
self.offset = offset
def error_ids(self):
for x in getbits(self.value, 16):
yield (self.level, self.offset + x)
class DEIF_Tank(device.CustomName, device.Tank, device.SubDevice):
raw_value_min = 0
raw_value_max = 100
raw_unit = '%'
def __init__(self, parent, subid, register):
self.register = register
super().__init__(parent, subid)
def device_init(self):
self.data_regs = [
Reg_s16(self.register, '/RawValue', 1, '%.0f %%'),
]
class DEIF_Generator(device.CustomName, device.ErrorId, device.Genset):
vendor_id = 'deif'
vendor_name = 'DEIF'
productid = 0xB049
productname = 'DEIF genset controller'
min_timeout = 0.5
default_access = 'input'
us_units = False
def temperature(self, v):
if self.us_units:
return (v - 32) * 5 / 9
else:
return v
def pressure(self, v):
if self.us_units:
return v * 6.89476
else:
return v * 100
def alarm_changed(self, reg):
eids = chain(self.err_reg.error_ids(), self.warn_reg.error_ids())
self.set_error_ids(eids)
def device_init(self):
self.info_regs = [
# /Serial -> not available
Reg_s16(500, '/FirmwareVersion', 1),
Reg_mapu16(5107, '/NrOfPhases', {
0: 3, # 3 phase 3W4
1: 3, # 3 phase 3W3
2: 2, # 2 phase L1|L3
3: 2, # 2 phase L1|L2
4: 1 # 1 phase L1
}, access='holding')
]
self.status_reg = Reg_bit(1018, '/StatusCode', bit=6, set=8)
self.warn_reg = Reg_DEIF_alarm(1000, 10, level='e',
onchange=self.alarm_changed)
self.err_reg = Reg_DEIF_alarm(1057, 1, level='w', offset=57 * 16,
onchange=self.alarm_changed)
self.data_regs = [
Reg_s16(504, '/Ac/L1/Voltage', 1, '%.0f V'),
Reg_s16(505, '/Ac/L2/Voltage', 1, '%.0f V'),
Reg_s16(506, '/Ac/L3/Voltage', 1, '%.0f V'),
Reg_s16(513, '/Ac/L1/Current', 1, '%.0f A'),
Reg_s16(514, '/Ac/L2/Current', 1, '%.0f A'),
Reg_s16(515, '/Ac/L3/Current', 1, '%.0f A'),
Reg_s16(516, '/Ac/L1/Power', 1/1000, '%.0f W'),
Reg_s16(517, '/Ac/L2/Power', 1/1000, '%.0f W'),
Reg_s16(518, '/Ac/L3/Power', 1/1000, '%.0f W'),
Reg_s16(519, '/Ac/Power', 1/1000, '%.0f W'),
Reg_s16(507, '/Ac/Frequency', 100, '%.1f Hz'),
Reg_s32b(536, '/Ac/Energy/Forward', 1, '%.0f kWh'),
Reg_s16(593, '/Engine/Speed', 1, '%.0f RPM', invalid=0), # EIC
Reg_s32b(554, '/Engine/OperatingHours', 1/3600, '%.0f s'),
Reg_s16(566, '/Engine/Starts', 1, '%.0f'),
Reg_s16(567, '/StarterVoltage', 10, '%.1f V'),
Reg_bit(1019, '/RemoteStartModeEnabled', bit=3),
self.status_reg,
self.warn_reg,
self.err_reg,
]
self.us_units = self.read_register(Reg_s16(4797, access='holding')) == 1
configs = self.read_modbus(776, 4)
def get_reg(conf_id, fallback=None):
"""
Value of register 776 indicates which sensor is connected
to Multi input 20 (register 583), 777 w.r.t. Multi Input 21 (register 584) etc.
Value mapping:
4 = RMI oil pressure
5 = RMI water temperature
6 = RMI fuel level
"""
try: return 583 + configs.registers.index(conf_id)
except: return fallback
fuel_reg = get_reg(6)
if fuel_reg is not None:
self.subdevices = [
DEIF_Tank(self, 0, fuel_reg),
]
# Check if oil pressure/coolant temp is configured on a analog input,
# otherwise fall back to EIC measurement
pres_reg = get_reg(4)
temp_reg = get_reg(5)
self.data_regs += [
Reg_DEIF_unit_s16(pres_reg or 595, '/Engine/OilPressure',
10 if pres_reg else 100, '%.0f kPa',
conv=self.pressure),
Reg_DEIF_unit_u16(26022, '/Engine/FuelDeliveryPressure',
100, '%.0f kPa', invalid=0,
conv=self.pressure),
Reg_DEIF_unit_s16(temp_reg or 594, '/Engine/CoolantTemperature',
1 if temp_reg else 10, '%.1f °C',
conv=self.temperature)
]
def get_unique(self):
return self.model.replace(' ', '').lower()
def device_init_late(self):
super().device_init_late()
is_running = bool(self.read_register(self.status_reg))
self.dbus.add_path('/Start', is_running, writeable=True,
onchangecallback=self._start_genset)
self.dbus.add_path('/EnableRemoteStartMode', 0, writeable=True,
onchangecallback=self._set_remote_start_mode)
def _start_genset(self, _, value):
# Auto start/stop
self.write_modbus(6, [1 | bool(value) << 11])
return True
def _set_remote_start_mode(self, _, value):
if value == 1:
self.write_modbus(6, [(1 | 1 << 13)]) # AUTO mode
return False
models = {
'AGC150GEN': { # Genset unit
'model': 'AGC 150 GEN',
'handler': DEIF_Generator,
},
'AGC150DGH': { # Genset HYBRID unit
'model': 'AGC 150 DGH',
'handler': DEIF_Generator,
},
'AGC150LDG': { # Genset PMS Lite unit
'model': 'AGC 150 LDG',
'handler': DEIF_Generator,
},
}
probe.add_handler(probe.ModelRegister(Reg_text(770, 6), models,